Verify the Application of Mechanical-Generated Temperatures

Ensure that the temperatures generated by Mechanical are the same as those consumed by the Maxwell. To verify the application of temperatures, check System Coupling's Transcript and EnSight-formatted Results files, as described in the following sections:

Review Temperatures in the Transcript

Review the Weighted Average values for the final coupling iteration to verify that the temperatures sent by Mechanical match those received by Maxwell.

Figure 22: Temperatures reported in the Transcript at Coupling Step 1, Iteration 5


+=============================================================================+
| COUPLING STEP = 1                                                           |
+=============================================================================+

+=============================================================================+
|                             COUPLING ITERATIONS                             |
+-----------------------------------------------------------------------------+
|                                     |      Source            Target         |
+-----------------------------------------------------------------------------+

...

+-----------------------------------------------------------------------------+
|                           COUPLING ITERATION = 5                            |
+-----------------------------------------------------------------------------+
| Ansys Electronics Desktop           |                                       |
|   Interface: CouplingInterface 1    |                                       |
|     Temp 1                          |             Converged                 |
|       RMS Change                    |     3.86E-03          3.89E-03        |
|       Weighted Average              |     3.74E+02          3.74E+02        |
|   Interface: CouplingInterface 2    |                                       |
|     Temp 2                          |             Converged                 |
|       RMS Change                    |     4.41E-03          4.75E-03        |
|       Weighted Average              |     3.79E+02          3.79E+02        |
|   Interface: CouplingInterface 3    |                                       |
|     Temp 3                          |             Converged                 |
|       RMS Change                    |     4.80E-03          4.96E-03        |
|       Weighted Average              |     3.80E+02          3.80E+02        |
+-----------------------------------------------------------------------------+


Visualize Temperature Results in EnSight

In EnSight, visualize the application of Mechanical-generated temperatures to Maxwell's electromagnetic analysis. Use the following variables:

  • Mechanical (nodes): Temperature__NS

  • Maxwell (elements): Temperature__ES

The palettes ranges are very similar and do not need to be adjusted, as shown in the image below.

Figure 23: Source-side and target-side temperatures at Coupling Step 1, Iteration 5

Source-side and target-side temperatures at Coupling Step 1, Iteration 5