Setting Up a Frequency Sweep with Harmonic Balance
Nexxim harmonic balance analysis supports a sweep of frequency using a local variable for the frequency value. (For DC analysis or transient analysis, no frequency parameters are predefined.) To perform a frequency sweep with harmonic balance analysis, perform the following steps:
- Under Circuit, select Add Nexxim Solution Setup. Select Harmonic Balance for the Analysis Type and 1-Tone or N-Tone for the Category as appropriate. Click Next.
- The Harmonic BalanceAnalysis dialog box appears.
- For N-Tone analysis, specify the No. of Tones. The Max. Harmonic Number table shows the frequency or frequencies. Specify the MaxK value for each frequency. To set up a sweep, click in the Value field for a frequency and enter the name of the local variable to be created. Press Return.
- The Add Variable dialog box opens. The local variable name you entered in the Parameter window appears in the Name field. Enter a default value for the local parameter in the Value field. Click the Local Variable radio button. Click OK.
- Repeat steps 3 and 4 until all desired frequencies have been set up as variables.
- Locate the Sweep Variables panel at the right side of the Solution Setup box.
- The Add/Edit Sweep dialog box opens. Select the local variable from the Variable field. Sweep options are:
- Single Value (enter the value and units)
- Linear Step (enter Start, Stop, and Step values and units)
- Linear count (enter Start, Stop, and Count values and units)
- Decade count (enter Start, Stop, and Count values and units)
- Octave count (enter Start, Stop, and Count values and units).
- Click Add.
- Repeat steps 7 and 8 until all frequency sweeps have been specified. If desired, add sweeps of component-value local variables using the procedure given under Setting Up a Local Variable on a Component Parameter.
- Click OK.
- Complete the Solution Setup information (Output Quantities, etc.), then click Finish.